This is another situation that
requires the overhead crane to rest for a while upon reaching both of the rail.
After a pre-determine time the overhead crane will re-start in the opposite
direction.
The control circuit of this system
is shown in Figure 8. Two times TR1 and TR2 are connected to the limit switches
Y and X respectively at terminal 3.
The
terminal no. 1 of the instantaneous contacts TR1(1-3) and TR2(1-3) are
connected to the terminals no. 3 of the limit switch Y and X respectively. The
delay contact TR1(6-8) and TR2(6-8) are connected to the contacts R(13-14) and
F(13-14) respectively.
Supposing
the overhead crane is moving in the forward (right) direction that means,
contactor F(A-B) is at energized and contactor R(A-b) is at de-energize
condition. When the overhead crane reaches the right end limit and touches the
limit switch Y, the contact Y(1-2) of limit switch Y will open to de-energize
contactor F(A-B). This will bring the overhead crane to stop moving in the
forward right direction and it will remain at stand still for a pre-determine
time set by timer TR1. Also the contact Y(1-3) of the Y limit switch will close
to de-energize timer TR1. The instantaneous contact TR1(1-3) will close
instantly to maintain TR1 continously energized.
After the pre-determine time set by TR1, the
delay contact TR1(6-8) will close to energized contactor R(A-B). This will
cause the overhead to start moving in the reverse (left) direction. At this
point the connection of limit switch Y contacts Y(1-2) will open and contact
Y(1-3) will close.
When the overhead crane reaches the left and it
touches the limit switch X, the contact X(1-2) of limit switch X will open to
de-energized contactor R and timer TR1. Instantaneous contact TR1(1-3) will
open. At this point the overhead crane will stop moving in the reverse (left)
direction and it will remain at stand still for pre-determine time set by timer
TR2. Also the contact X(1-3) of the X limit will close to energized timer TR2.
The instantaneous contact TR2(1-3) will close instantly to maintain TR2
continuosly energized. After the pre-determine time set by timer TR2, the delay
contact TR2(6-8) will close to energize contactor F(A-B).
When the contactor F(A-B) is energized, it will
cause the overhead crane to start moving in the forward (right) direction.
Immediately after, the connection of contact X(1-3) will open and contact
X(1-2) will close again. Timer TR2 will remain energize because its
instantaneous contact TR2(1-3) is maintain close. Timer TR2 will be
de-energized when the overhead crane reach the right end limit and touches
limit switch Y.